| Input Voltage: 220–240 VAC |
LED Emergency Conversion Module with Automatic Self-test |
IP Grade: IP20; protection against accidental contact with live parts relies on the luminaire enclosure |
Short Circuit Protection: Automatic recovery |
| Frequency: 50/60 Hz |
Output Type: Constant power |
Insulation Class: Class II |
Overload Protection: Automatic recovery |
| Input Current: 50 mA |
Emergency Output Power: 4 W |
Installation: Built-in |
No-load Protection: Automatic recovery |
| Input Power: ≤ 5 W |
Output Voltage: 50–300 VDC; maximum 350 VDC; for 15–100 LEDs |
Dimensions: 179 × 30 × 21 mm (L × W × H) |
Automatic Initial Test: Checks LED load, battery, LED driver and emergency module |
| Power Factor: > 0.5 |
Battery: LiFePO₄, 6.4 V / 3.2 Ah |
Connection Method: Flying leads |
Automatic Functional Test: 10 seconds every 7 days |
| No-load Power Consumption: ≤ 1.5 W (230 VAC) |
Rated Emergency Duration: 3 hours |
Operating Temperature: 0 to +50 °C |
Automatic Duration Test: Full-duration test every 180 days |
| Inrush Current: ≤ 36 A / 420 µs (230 VAC, full load) |
Charging Time: ≥ 16 hours; trickle charging; charging current 0–250 mA |
Storage Temperature: −20 to +45 °C |
Battery Protection: Deep discharge protection and reverse polarity protection at the battery connector |
| Surge Immunity: 1 kV (L–N) |
Lifetime: 50000 h at Ta = 50 °C / Tc = 70 °C |
Maximum Tc Temperature: 70 °C |
Status Indication: Two-colour LED for charging, self-test, fully charged battery and faults |
|
Warranty: 3 years; failure rate < 10000 ppm |
Humidity: 10–90 % RH |
Rest Mode: Activated during emergency operation by pressing the test switch for more than 3 seconds |
|
|
|
Test Timer Reset: Cycle the unswitched mains supply 3 times within 1 minute |
|
|
|
Application: Maintained or non-maintained emergency lighting, depending on wiring; additional relay for controlling the standard LED driver |